Technical Specification
OUTPUT POWER 1500RPM 50HZ Engine Alternator Alternator Dimension(L*W*H mm)
No Standby KVA Standby KW Prime
KVA
Prime
KW
Perkins-LOVOL
Model
NEWAGE Stamford SPARK Open genset Silent genset
01. 25 20 23 18 1003G PI144E SPG141E 2000x730x1550 2330*1110*1830
02. 30 24 28 22 1003G PI144F SPG141F 2000x730x1550 2330*1110*1830
03. 33 26.5 30 24 1003TG PI144H SPG141G 2000x730x1550 2330*1110*1830
04. 40 32 37 29.5 1003TG PI144J SPG241C 2000x730x1550 2330*1110*1830
05. 45 36 41 33 1003TG PI144K SPG241CB 2000x730x1550 2330*1110*1830
06. 49 39 44 35 1003TG UCI224D SPG241D 2000x730x1550 2330*1110*1830
07. 34 27 31 25 1004G PI144H SPG141G 2200x730x1700 2330*1110*1830
08. 41 33 38 30 1004G PI144J SPG241C 2200x730x1700 2330*1110*1830
09. 46 37 42 34 1004G PI144K SPG241CB 2200x730x1700 2480*1110*1830
10. 50 40 45 36 1004G UCI224D SPG241D 2200x730x1700 2480*1110*1830
11. 55 44 50 40 1004TG UCI224D SPG241D 2200x730x1700 2480*1110*1830
12. 65 52 60 48 1004TG UCI224E SPG241E 2200x730x1700 2480*1110*1830
13. 76 61 70 56 1004TG UCI224F SPG241F 2200x730x1700 2480*1110*1830
14. 94 75 85 68 1006TG1A UCI224G SPG241G 2645*730*1700 2930*1110*1930
15. 100 80 90 72 1006TG1A UCI274C SPG341C 2645*730*1700 2930*1110*1930
16. 110 88 100 80 1006TG2A UCI274C SPG341C 2645*730*1700 2930*1110*1930
17. 125 100 114 91 1006TAG UCI274D SPG341D 2645*730*1700 2930*1110*1930
18. 150 120 135 108 1006TAG UCI274E SPG341E 2645*730*1700 2930*1110*1930
Diesel genset with Lovol (Perkins) engine and Stamford alternator
A. Main specifications
01. Lovol engine brand output range: 18kW (24kVA) - 112kW (140kVA)
02. Engine model: 1003G, 1004G, 1004TG, 1006TG1A, 1006TG2A, 1006TAG
03. Alternator: Stamford, Leroy Somer, Marathon series
04. Water-cooled
05. 8hrs operation base tank
06. Key start / auto start
07. Sound-proof / weather-proof canopy is optional
08. 230 / 400V AC, 50Hz / 60Hz, 0.8pF three-phase and four wires alternating current output
09. Frequency: <3%
10. Frequency at stable state: <0.5%
11. Frequency deviation at instantaneous state: ≤+10%
12. Frequency return time: ≤3s
13. Voltage deviation at stable state: ≤+ -1%
14. Voltage deviation at instantaneous state: ≤+20%
15. Voltage return time: ≤4s
16. Voltage modulation: ≤0.3%
17. Standard configuration of gensets
(A)Engine: Perkins diesel engine (B) Engine type: Water-cooled, in line four-stoke, dry cylinder liner, direct injection (C) Alternator: Brushless and "H" class insulation
18. Control system
(A) Automatic alarm system: The unit has the acousto-optics alarm system and Arrestor for any situation as the start defeat, the water is over temperature, The oil pulls down, over speed, over load and over current.
( B) Operation display :
(1)Unit voltage, tri-phase load current and frequency display (2) Water temperature, oil pressure display (3) Fuel level, fuel temperature display. (4) Audible and visual alarm lamps and buzzers.
19. Starting system: DC alternator is used to start engine
20. Short circuit protection: MCCB air switch
21. Cooling system: Combined cooling water tank fitted to meet the requirement of radiation at ambient temperature 40 degree
22. Filter system: Oil, fuel and air filter
23. Accessories: Exhaust elbow, bellow, muffler
24. Supply standard collocation
(A) Diesel engine with all accessories, 3 filter, electric systems. (B) Alternator (C) Steel structure (D) Fan and water tank cooling system. (E)Flangeconnector (F) 12 / 24V starting motor and charge engine (G) Air cleaner, fuel cleaner, oil cleaner (H) On-board control panel (I) MCCB air conservation switch. (J) 12 / 24V starting accumulator and battery line.(K) Set shock absorber. (L) High-efficient silencer.